Pole Mounted Circuit Breaker
KGVZ 15-38kV Solid-Dielectric Automatic Circuit Recloser
Model KGVZ
CANGO is an automatic circuit recloser supplier for 15-38kV overhead lines and substations, with KGVZ switchgear and BC300 or BC500 control.
Share your rated data, quantity and project requirements.
Product Overview
KGVZ is a solid-dielectric automatic circuit recloser designed for overhead distribution lines and distribution substations up to 38 kV. The switchgear uses vacuum interrupters encapsulated in hydrophobic epoxy resin and a ganged magnetic actuator for three-phase opening and closing.
The operating mechanism is enclosed in a stainless-steel tank with a light-grey powder-coated finish. KGVZ15,KGVZ27, and KGVZ38 configurations cover 15.5 kV, 27 kV, and 38 kV voltage classes with 630 A or 800 A continuous-current options shown in the technical table.
The recloser is supplied with a BC300 or BC500 microprocessor controller for protection, control, monitoring, metering, event recording, and communications. Utilities, EPC contractors, distributors, and automation project buyers should provide the feeder study, protection settings, communication protocol, mounting arrangement, quantity, and destination for technical review and quotation.
The product guide states that the KGVZ series has been type-tested in CANGO‘s independent laboratory.
Technical Specifications
| Selection | Current and short-circuit ratings | Insulation | Construction | Mechanical and switching | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Voltage class / frequency | Model | Rated continuous current (Ir/A) | Rated short-circuit duration (Tk/s) | Rated short-circuit making current (Isc/kA) | Rated short-circuit breaking current (Ima/kA) | Lightning impulse withstand voltage (Up/kV) | Short-duration power-frequency withstand voltage (Ud/kV) | Impedance between contacts (microohm) | Creepage distance phase-to-earth (mm) | Clearance phase-to-phase (mm) | Minimum clearance phase-to-earth (mm) | Weight (kg) | Line charging current (A) | Cable charging current (A) | Max. interrupting / closing time (ms) |
| 15.5 kV / 50/60 Hz | KGVZ15-630-12-N | 630 | 3 | 12.5 | 31.5 | 110 | 50 | 60 | 960 | 320 | 270 | 130 | 2 | 10 | 40 / 60 |
| 15.5 kV / 50/60 Hz | KGVZ15-800-12-N | 800 | 3 | 12.5 | 31.5 | 110 | 50 | 60 | 960 | 320 | 270 | 130 | 2 | 10 | 40 / 60 |
| 15.5 kV / 50/60 Hz | KGVZ15-630-16-N | 630 | 3 | 16 | 40 | 110 | 50 | 60 | 960 | 320 | 270 | 130 | 2 | 10 | 40 / 60 |
| 15.5 kV / 50/60 Hz | KGVZ15-800-16-N | 800 | 3 | 16 | 40 | 110 | 50 | 60 | 960 | 320 | 270 | 130 | 2 | 10 | 40 / 60 |
| 27 kV / 50/60 Hz | KGVZ27-630-12-N | 630 | 3 | 12.5 | 31.5 | 130 | 60 | 60 | 1080 | 320 | 270 | 130 | 5 | 25 | 40 / 60 |
| 27 kV / 50/60 Hz | KGVZ27-800-12-N | 800 | 3 | 12.5 | 31.5 | 130 | 60 | 60 | 1080 | 320 | 270 | 130 | 5 | 25 | 40 / 60 |
| 27 kV / 50/60 Hz | KGVZ27-630-16-N | 630 | 3 | 16 | 40 | 130 | 60 | 60 | 1080 | 320 | 270 | 130 | 5 | 25 | 40 / 60 |
| 27 kV / 50/60 Hz | KGVZ27-800-16-N | 800 | 3 | 16 | 40 | 130 | 60 | 60 | 1080 | 320 | 270 | 130 | 5 | 25 | 40 / 60 |
| 27 kV / 50/60 Hz | KGVZ27-630-16-H | 630 | 3 | 16 | 40 | 170 | 70 | 60 | 1290 | 320 | 350 | 148 | 5 | 25 | 40 / 60 |
| 27 kV / 50/60 Hz | KGVZ27-800-16-H | 800 | 3 | 16 | 40 | 170 | 70 | 60 | 1290 | 320 | 350 | 148 | 5 | 25 | 40 / 60 |
| 38 kV / 50/60 Hz | KGVZ38-630-12-N | 630 | 3 | 12.5 | 31.5 | 170 | 70 | 60 | 1290 | 320 | 350 | 148 | 5 | 40 | 40 / 60 |
| 38 kV / 50/60 Hz | KGVZ38-800-12-N | 800 | 3 | 12.5 | 31.5 | 170 | 70 | 60 | 1290 | 320 | 350 | 148 | 5 | 40 | 40 / 60 |
| 38 kV / 50/60 Hz | KGVZ38-630-16-N | 630 | 3 | 16 | 40 | 170 | 70 | 60 | 1290 | 320 | 350 | 148 | 5 | 40 | 40 / 60 |
| 38 kV / 50/60 Hz | KGVZ38-800-16-N | 800 | 3 | 16 | 40 | 170 | 70 | 60 | 1290 | 320 | 350 | 148 | 5 | 40 | 40 / 60 |
Installation Dimensions / Drawing
| Voltage class | Unit | A | B | C | D | E | F |
|---|---|---|---|---|---|---|---|
| 15.5 kV | mm | 360 | 380 | 910 | 580 | 310 | 1000 |
| 27 kV | mm | 360 | 380 | 910 | 580 | 310 | 1000 |
| 38 kV | mm | 380 | 380 | 1030 | 640 | 310 | 1000 |


Applications
- Overhead distribution line protection and sectionalizing
- Distribution substation feeder protection
- Remote distribution automation and feeder control
- Utility and industrial medium-voltage distribution networks
Ordering Instructions / Information Required for Quotation
ORDERING INSTRUCTIONS
- Provide the system voltage, frequency, continuous current, short-circuit duty, feeder single-line diagram, and protection-coordination study.
- State the required KGVZ voltage class and model, BC300 or BC500 controller, protection functions, reclosing sequence, metering, and event-recording requirements.
- Confirm RS485, RS232, or Ethernet communication interfaces and the required Modbus, IEC 60870-5, or DNP3.0 protocol.
- Provide the pole or substation mounting arrangement, auxiliary supply, quantity, project country, applicable standard, and delivery requirement.