Skip to content
CANGO
SC(B)14-NX2 Dry-Type Distribution Transformer

Power Transformer

SC(B)14-NX2 Dry-Type Distribution Transformer

Model SC(B)14-NX2

CANGO supplies SC(B)14-NX2 Level 2 Energy-Efficiency Dry-Type Transformer for commercial and industrial electrical projects. Send rated data, drawings.

Request a quote

Share your rated data, quantity and project requirements.

Project configuration reviewTechnical documentation support

Product Overview

SC(B)14-NX2 level 2 energy-efficiency dry-type transformer is presented in the supplemental technical document as an energy-saving dry-type transformer developed according to. It is commonly used for commercial and industrial electrical projects and indoor distribution systems, with the final selection based on rated data, drawings, and site conditions.

utilities, EPC contractors, transformer distributors, industrial project owners, and electrical engineering companies can request configuration review for level 2 dry type transformer. Please send capacity, voltage combination, tap range, connection group, cooling or insulation type, loss data, impedance, and installation environment, quantity, destination, and any project standard requirements for quotation.

Model and Meaning

SC(B)14-NX2 level 2 energy-efficiency dry-type transformer model and meaning diagram

Technical Specifications

Main Product Performance Parameters of SC(B)14-NX2 10 kV Level 2 Dry-Type Transformer

Model Rated capacity (kVA) Connection group High voltage (kV) Tap range (%) Low voltage (kV) No-load loss (W) Load loss (W) No-load current (%) Short-circuit impedance (%)
SC(B)14-30/10-NX2 30 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 130 640 2 4
SC(B)14-50/10-NX2 50 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 185 900 2 4
SC(B)14-80/10-NX2 80 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 250 1240 1.5 4
SC(B)14-100/10-NX2 100 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 270 1415 1.5 4
SC(B)14-125/10-NX2 125 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 320 1665 1.3 4
SC(B)14-160/10-NX2 160 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 365 1915 1.3 4
SC(B)14-200/10-NX2 200 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 420 2275 1.1 4
SC(B)14-250/10-NX2 250 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 490 2485 1.1 4
SC(B)14-315/10-NX2 315 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 600 3125 1 4
SC(B)14-400/10-NX2 400 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 665 3590 1 4
SC(B)14-500/10-NX2 500 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 790 4390 1 4
SC(B)14-630/10-NX2 630 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 910 5290 0.85 4
SC(B)14-630/10-NX2 630 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 885 5365 0.85 6
SC(B)14-800/10-NX2 800 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 1035 6265 0.85 6
SC(B)14-1000/10-NX2 1000 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 1205 7315 0.85 6
SC(B)14-1250/10-NX2 1250 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 1420 8720 0.85 6
SC(B)14-1600/10-NX2 1600 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 1665 10555 0.85 6
SC(B)14-2000/10-NX2 2000 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 2075 13005 0.7 6
SC(B)14-2500/10-NX2 2500 Dyn11 / Yyn0 6 / 6.3 / 6.6 / 10 / 10.5 / 11 +/-2.5% / +/-5%; selected capacities +/-2 x 2.5% / +/-5% 0.4 2450 15445 0.7 6

Installation Dimensions / Drawing

ForSC(B)14-NX2, confirm the capacity-specific outline dimensions, installation base, terminal position, cooling clearance, and lifting / handling requirements. Use the confirmed technical table, project drawing, and site installation plan as the final dimensional reference before ordering or installation.

Applications

SC(B)14-NX2 is mainly selected for commercial and industrial electrical projects and indoor distribution systems. The final application should match the confirmed level 2 dry type transformer, rated data, and site installation conditions.
  • Commercial and industrial electrical projects
  • Indoor distribution systems
  • Projects requiring level 2 energy-efficiency dry-type transformers

Ordering Instructions / Information Required for Quotation

ForSC(B)14-NX2, send capacity, voltage combination, tap range, connection group, cooling or insulation type, loss data, impedance, and installation environment, quantity, destination, and the expected delivery schedule. The engineering review will be based on the selected level 2 dry type transformer and project drawing.

ORDERING INSTRUCTIONS

  • State the required SC(B)14-NX2 configuration, quantity, project destination, and intended application.
  • Provide capacity, voltage combination, tap range, connection group, impedance, loss data, cooling or insulation type, and installation environment for technical review.
  • Confirm the capacity-specific outline dimensions, installation base, terminal position, cooling clearance, and lifting / handling requirements before final production or installation planning.
  • List any special environmental, wiring, communication, metering, protection, or component requirements in the inquiry.

Tell us what
you need.

Share your equipment specifications and project requirements. Our team will help you review the next step.

Scope
Equipment · Projects · Configuration
Email
sales@cangopower.com

Project details

Fields marked * are required.

Opens a draft in your email application. Review and send it to complete your inquiry. Privacy Policy