Skip to content
CANGO
KYN28-24 24kV Metal-Clad Switchgear

Medium-Voltage Switchgear

KYN28-24 24kV Metal-Clad Switchgear

Model KYN28-24

24 kV metal-clad withdrawable switchgear for receiving, distributing, controlling and protecting electrical power. Review busbar current, short-circuit duty and circuit-breaker configuration against the equipment schedule.

Request a quote

Share your rated data, quantity and project requirements.

View this model in our 2026 catalog ↗

Project configuration reviewTechnical documentation support

Product Overview

KYN28-24 armored removable AC metal-enclosed switchgear is used to receive and distribute electrical energy and to control, protect, and monitor circuits in three-phase AC. It is commonly used for medium-voltage power distribution systems and distribution rooms requiring removable switchgear, with the final selection based on rated data, drawings, and site conditions.

EPC companies, electrical contractors, utility project teams, panel builders, and industrial buyers can request configuration review for medium voltage switchgear. Please send single-line diagram, rated voltage, rated current, short-circuit level, protection scheme, busbar arrangement, and cabinet layout, quantity, destination, and any project standard requirements for quotation.

Model and Meaning

  • K: armored switchgear
  • Y: removable type
  • N: indoor type
  • 28: design serial number
  • 24: rated-voltage class
  • Confirm the selected vacuum circuit breaker and ordered circuit configuration
KYN28-24 armored removable ac metal-enclosed switchgear model and meaning diagram

Technical Specifications

KYN28-24 Technical Parameter Table
Review the KYN28-24 values, units, rated data, and project requirements before quotation.
Item Unit Data
Rated voltage kV 24
Rated frequency Hz 50
Rated current of circuit breaker A 630, 1250, 1600, 2000, 2500, 3150, 4000
Rated current of switchgear A 630, 1250, 1600, 2000, 2500, 3150, 4000
Rated dynamic stability current (4s) kA 16, 20, 25, 31.5, 40, 50
Rated stability current (peak value) kA 40, 50, 63, 80, 100, 125
Rated short-circuit breaking current kA 16, 20, 25, 31.5, 40, 50
Rated short-circuit closing current (peak value) kA 40, 50, 63, 80, 100, 125
Rated insulation level 1 min power frequency withstand voltage Between poles, pole to ground kV 65
Between breaks kV 79
Lightning impulse withstand voltage (peak value) Between poles, pole to ground, and break kV 125
Between breaks kV 145
Protection level Housing IP4X, isolation room, circuit breaker room door open IP2X
Note: The short-circuit capacity of the current transformer is considered separately.

Installation Dimensions / Drawing

KYN28-24 armored removable switchgear cabinet structure diagram
KYN28-24 cabinet structure diagram showing busbar room, circuit breaker trolley room, cable room, relay instrument room, and key internal components for project layout review.

Applications

KYN28-24 is mainly selected for medium-voltage power distribution systems and distribution rooms requiring removable switchgear. The final application should match the confirmed medium voltage switchgear, rated data, and site installation conditions.
  • Medium-voltage power distribution systems
  • Distribution rooms requiring removable switchgear
  • Electrical projects requiring circuit protection and monitoring

Ordering Instructions / Information Required for Quotation

ForKYN28-24, send single-line diagram, rated voltage, rated current, short-circuit level, protection scheme, busbar arrangement, and cabinet layout, quantity, destination, and the expected delivery schedule. The engineering review will be based on the selected medium voltage switchgear and project drawing.

ORDERING INSTRUCTIONS

  • Provide the main-circuit scheme number, purpose, single-line system diagram, rated voltage, rated current, rated short-circuit breaking current, distribution-room layout, and switchgear arrangement.
  • State the requirements for switchgear control, measurement, protection, locking, and automatic devices.
  • Provide the models, specifications, and quantities of the main electrical components.
  • If a busbar bridge is required, provide its rated current-carrying capacity, span, height from the ground, and other requirements.
  • State any special environmental conditions and other special requirements.

Tell us what
you need.

Share your equipment specifications and project requirements. Our team will help you review the next step.

Scope
Equipment · Projects · Configuration
Email
sales@cangopower.com

Project details

Fields marked * are required.

Opens a draft in your email application. Review and send it to complete your inquiry. Privacy Policy